Transformer loading and solar headroom calculator
Enter your transformer rating and present maximum demand, and the solar or storage you plan to add. See the loading today, the full-load current and incomer rating at 415 V, how much solar the transformer can take without reverse-flow problems, and whether an upgrade is needed. Runs in your browser; nothing is uploaded.
This calculator needs JavaScript. If nothing appears below, enable JavaScript or send us your bill and we will run the numbers for you.
Your numbers
Fill in the required figures to begin.
Unlock the detailed report
The headline numbers are free. The full breakdown, sizing and payback are emailed to you and unlocked here once you verify your work email.
- Full breakdown of every figure
- System size, capex and payback
- What to do next, flagged by our engineers
- A copy emailed to you, plus one-click request for the free feasibility study
One-time code to your email, nothing else. We do not share your details.
What limits solar on an existing transformer
Loading
Loading is maximum demand divided by rating. Above about 80 per cent there is little room for growth, and above 100 per cent the transformer is being overloaded for part of the day. Storage that shaves the peak is one way to buy headroom without a new transformer.
Reverse flow
At midday solar output minus your minimum load flows back through the transformer towards the grid. That reverse flow must stay within the transformer rating and within what the DISCOM allows for your connection. If the plant is designed for zero export, the EMS curtails the inverters instead, and the reverse-flow figure tells you how much curtailment to expect.
Incomer rating
Full-load current at 415 V is rating divided by root three times voltage. The incomer air circuit breaker is the next standard rating above it. Adding solar on the same bus does not raise the incomer current, because solar reduces what the incomer carries, but the bus and its short-circuit rating still have to be checked for the added infeed.
Can I add solar to a transformer that is already at 90 per cent?
Yes, because solar reduces the transformer loading in daylight rather than adding to it. The checks are reverse flow at minimum load and the short-circuit contribution of the inverters on the bus, both of which the feasibility study covers.
What does the DISCOM allow for reverse flow?
It depends on the connection agreement and the current GERC order. We design for self-consumption with a zero-export relay unless export is explicitly permitted, so reverse flow at the meter is controlled.
Does a battery add to transformer loading?
Only while charging from the grid, which the EMS schedules at low-load hours. Discharging reduces loading, which is the point of peak shaving.